Overhead power line
This article includes a list of general references, but it lacks sufficient corresponding inline citations. (August 2010) |
An overhead power line is a structure used in
Construction
Towers for support of the lines are made of wood (as-grown or laminated), steel or aluminum (either lattice structures or tubular poles), concrete, and occasionally reinforced plastics. The bare wire conductors on the line are generally made of aluminum (either plain or
Classification by operating voltage
Overhead power transmission lines are classified in the electrical power industry by the range of voltages:
- Low voltage (LV) – less than 1000 volts, used for connection between a residential or small commercial customer and the utility.
- Medium voltage (MV; distribution) – between 1000 volts (1 kV) and 69 kV, used for distribution in urban and rural areas.
- High voltage (HV; subtransmissionless than 100 kV; subtransmission or transmission at voltages such as 115 kV and 138 kV), used for sub-transmission and transmission of bulk quantities of electric power and connection to very large consumers.
- Extra high voltage (EHV; transmission) – from 345 kV, up to about 800 kV,[2][page needed] used for long distance, very high power transmission.
- Ultra high voltage (UHV) – higher than 800 kV. The Financial Times reported UHV lines are a "game changer", making a global electricity grid potentially feasible. StateGrid said that compared to conventional lines, UHV enables the transmission of five times more power, over six times the distance.[3]
Structures
Structures for overhead lines take a variety of shapes depending on the type of line. Structures may be as simple as wood
Each structure must be designed for the loads imposed on it by the conductors.[1] The weight of the conductor must be supported, as well as dynamic loads due to wind and ice accumulation, and effects of vibration. Where conductors are in a straight line, towers need only resist the weight since the tension in the conductors approximately balances with no resultant force on the structure. Flexible conductors supported at their ends approximate the form of a catenary, and much of the analysis for construction of transmission lines relies on the properties of this form.[1]
A large transmission line project may have several types of towers, with "tangent" ("suspension" or "line" towers, UK) towers intended for most positions and more heavily constructed towers used for turning the line through an angle, dead-ending (terminating) a line, or for important river or road crossings. Depending on the design criteria for a particular line, semi-flexible type structures may rely on the weight of the conductors to be balanced on both sides of each tower. More rigid structures may be intended to remain standing even if one or more conductors is broken. Such structures may be installed at intervals in power lines to limit the scale of cascading tower failures.[1]
Foundations for tower structures may be large and costly, particularly if the ground conditions are poor, such as in wetlands. Each structure may be stabilized considerably by the use of guy wires to counteract some of the forces applied by the conductors.
Power lines and supporting structures can be a form of visual pollution. In some cases the lines are buried to avoid this, but this "undergrounding" is more expensive and therefore not common.
For a single wood utility pole structure, a pole is placed in the ground, then three crossarms extend from this, either staggered or all to one side. The insulators are attached to the crossarms. For an "H"-type wood pole structure, two poles are placed in the ground, then a crossbar is placed on top of these, extending to both sides. The insulators are attached at the ends and in the middle. Lattice tower structures have two common forms. One has a pyramidal base, then a vertical section, where three crossarms extend out, typically staggered. The strain insulators are attached to the crossarms. Another has a pyramidal base, which extends to four support points. On top of this a horizontal truss-like structure is placed.
A grounded wire is sometimes strung along the tops of the towers to provide lightning protection. An optical ground wire is a more advanced version with embedded optical fibers for communication. Overhead wire markers can be mounted on the ground wire to meet International Civil Aviation Organization recommendations.[6] Some markers include flashing lamps for night-time warning.
Circuits
A single-circuit transmission line carries conductors for only one circuit. For a three-phase system, this implies that each tower supports three conductors.
A double-circuit transmission line has two circuits. For three-phase systems, each tower supports and insulates six conductors. Single phase AC-power lines as used for
In HVDC systems typically two conductors are carried per line, but in rare cases only one pole of the system is carried on a set of towers.
In some countries like Germany most power lines with voltages above 100 kV are implemented as double, quadruple or in rare cases even hextuple power line as
The largest double-circuit transmission line is the
-
A single-circuit 138 kV line (top) with distribution wires (bottom)
-
A double-circuit line
-
Parallel single-circuit lines
-
Four circuits on one tower line
-
six circuits of three different types
-
Various powerlines (110/220 kV) in Germany with double and quadruple circuits
Insulators
At the end of the 19th century, the limited electrical strength of
Insulators are usually made of wet-process
Suspension insulators are made of multiple units, with the number of unit insulator disks increasing at higher voltages. The number of disks is chosen based on line voltage, lightning withstand requirement, altitude, and environmental factors such as fog, pollution, or salt spray. In cases where these conditions are suboptimal, longer insulators must be used. Longer insulators with longer creepage distance for leakage current, are required in these cases. Strain insulators must be strong enough mechanically to support the full weight of the span of conductor, as well as loads due to ice accumulation, and wind.[9]
Porcelain insulators may have a semi-conductive glaze finish, so that a small current (a few milliamperes) passes through the insulator. This warms the surface slightly and reduces the effect of fog and dirt accumulation. The semiconducting glaze also ensures a more even distribution of voltage along the length of the chain of insulator units.
Polymer insulators by nature have hydrophobic characteristics providing for improved wet performance. Also, studies have shown that the specific creepage distance required in polymer insulators is much lower than that required in porcelain or glass. Additionally, the mass of polymer insulators (especially in higher voltages) is approximately 50% to 30% less than that of a comparative porcelain or glass string. Better pollution and wet performance is leading to the increased use of such insulators.
Insulators for very high voltages, exceeding 200 kV, may have
Conductors
The most common conductor in use for transmission today is
While larger conductors lose less energy due to lower
Since a conductor is a flexible object with uniform weight per unit length, the shape of a conductor strung between two towers approximates that of a
Two such conductors that offer reduced thermal sag are known as composite core conductors (ACCR and ACCC conductor). In lieu of steel core strands that are often used to increase overall conductor strength, the ACCC conductor uses a carbon and glass fiber core that offers a coefficient of thermal expansion about 1/10 of that of steel. While the composite core is nonconductive, it is substantially lighter and stronger than steel, which allows the incorporation of 28% more aluminum (using compact trapezoidal-shaped strands) without any diameter or weight penalty. The added aluminum content helps reduce line losses by 25 to 40% compared to other conductors of the same diameter and weight, depending upon electric current. The carbon core conductor's reduced thermal sag allows it to carry up to twice the current ("ampacity") compared to all-aluminum conductor (AAC) or ACSR.
The power lines and their surroundings must be
Bundle conductors
For transmission of power across long distances, high voltage transmission is employed. Transmission higher than 132 kV poses the problem of corona discharge, which causes significant power loss and interference with communication circuits. To reduce this corona effect, it is preferable to use more than one conductor per phase, or bundled conductors.[15]
Bundle conductors consist of several parallel cables connected at intervals by spacers, often in a cylindrical configuration. The optimum number of conductors depends on the current rating, but typically higher-voltage lines also have higher current. American Electric Power[16] is building 765 kV lines using six conductors per phase in a bundle. Spacers must resist the forces due to wind, and magnetic forces during a short-circuit.
Bundled conductors reduce the voltage gradient in the vicinity of the line. This reduces the possibility of corona discharge. At
Bundled conductors cool themselves more efficiently due to the increased surface area of the conductors, further reducing line losses. When transmitting alternating current, bundle conductors also avoid the reduction in
While wind resistance is higher, wind-induced oscillation can be damped at bundle spacers. The ice and wind loading of bundled conductors will be greater than a single conductor of the same total cross section, and bundled conductors are more difficult to install than single conductors.
Ground wires
Overhead power lines are often equipped with a ground conductor (shield wire, static wire, or overhead earth wire). The ground conductor is usually grounded (earthed) at the top of the supporting structure, to minimize the likelihood of direct lightning strikes to the phase conductors.
At some HVDC converter stations, the ground wire is used also as the electrode line to connect to a distant grounding electrode. This allows the HVDC system to use the earth as one conductor. The ground conductor is mounted on small insulators bridged by lightning arrestors above the phase conductors. The insulation prevents electrochemical corrosion of the pylon.
Medium-voltage distribution lines may also use one or two shield wires, or may have the grounded conductor strung below the phase conductors to provide some measure of protection against tall vehicles or equipment touching the energized line, as well as to provide a neutral line in Wye wired systems.
On some power lines for very high voltages in the former Soviet Union, the ground wire is used for PLC systems and mounted on insulators at the pylons.
Insulated conductors and cable
Overhead insulated cables are rarely used, usually for short distances (less than a kilometer). Insulated cables can be directly fastened to structures without insulating supports. An overhead line with bare conductors insulated by air is typically less costly than a cable with insulated conductors.
A more common approach is "covered" line wire. It is treated as bare cable, but often is safer for wildlife, as the insulation on the cables increases the likelihood of a large-wing-span raptor to survive a brush with the lines, and reduces the overall danger of the lines slightly. These types of lines are often seen in the eastern United States and in heavily wooded areas, where tree-line contact is likely. The only pitfall is cost, as insulated wire is often costlier than its bare counterpart. Many utility companies implement covered line wire as jumper material where the wires are often closer to each other on the pole, such as an underground riser/pothead, and on reclosers, cutouts and the like.
Dampers
Because power lines can suffer from aeroelastic flutter driven by wind, Stockbridge dampers are often attached to the lines to reduce the vibrations.
Compact transmission lines
This section needs additional citations for verification. (March 2012) |
A compact overhead transmission line requires a smaller right of way than a standard overhead powerline. Conductors must not get too close to each other. This can be achieved either by short span lengths and insulating crossbars, or by separating the conductors in the span with insulators. The first type is easier to build as it does not require insulators in the span, which may be difficult to install and to maintain.
Examples of compact lines are:
- Lutsk compact overhead powerline 50°46′29″N 25°23′07″E / 50.774673°N 25.385215°E
- Hilpertsau-Weisenbach compact overhead line 48°44′16″N 8°21′20″E / 48.737898°N 8.355660°E
Compact transmission lines may be designed for voltage upgrade of existing lines to increase the power that can be transmitted on an existing right of way.[18]
Low voltage
Low voltage overhead lines may use either bare conductors carried on glass or ceramic insulators or an aerial bundled cable system. The number of conductors may be anywhere between two (most likely a phase and neutral) up to as many as six (three phase conductors, separate neutral and earth plus street lighting supplied by a common switch); a common case is four (three phase and neutral, where the neutral might also serve as a protective earthing conductor).
Train power
Overhead lines or overhead wires are used to transmit electrical energy to trams, trolleybuses or trains. Overhead line is designed on the principle of one or more overhead wires situated over rail tracks. Feeder stations at regular intervals along the overhead line supply power from the high-voltage grid. For some cases low-frequency AC is used, and distributed by a special
Further applications
Overhead lines are also occasionally used to supply transmitting antennas, especially for efficient transmission of long, medium and short waves. For this purpose a staggered array line is often used. Along a staggered array line the conductor cables for the supply of the earth net of the transmitting antenna are attached on the exterior of a ring, while the conductor inside the ring, is fastened to insulators leading to the high-voltage standing feeder of the antenna.
Use of area under overhead power lines
Use of the area below an overhead line is limited because objects must not come too close to the energized conductors. Overhead lines and structures may shed ice, creating a hazard. Radio reception can be impaired under a power line, due both to shielding of a receiver antenna by the overhead conductors, and by partial discharge at insulators and sharp points of the conductors which creates radio noise.
In the area surrounding the overhead lines it is dangerous to risk interference; e.g. flying kites or balloons, using ladders or operating machinery.
Overhead distribution and transmission lines near
Construction of overhead power lines, especially in wilderness areas, may have significant environmental effects. Environmental studies for such projects may consider the effect of bush clearing, changed migration routes for migratory animals, possible access by predators and humans along transmission corridors, disturbances of fish habitat at stream crossings, and other effects.
Aviation accidents
General aviation, hang gliding, paragliding, skydiving, balloon, and kite flying must avoid accidental contact with power lines. Nearly every kite product warns users to stay away from power lines. Deaths occur when aircraft crash into power lines. Some power lines are marked with obstruction markers, especially near air strips or over waterways that may support floatplane operations. The placement of power lines sometimes use up sites that would otherwise be used by hang gliders.[19][20]
History
The first transmission of electrical impulses over an extended distance was demonstrated on July 14, 1729 by the physicist Stephen Gray.[citation needed] The demonstration used damp hemp cords suspended by silk threads (the low resistance of metallic conductors not being appreciated at the time).
However the first practical use of overhead lines was in the context of
In 1912 the first 110 kV-overhead power line entered service followed by the first 220 kV-overhead power line in 1923. In the 1920s RWE AG built the first overhead line for this voltage and in 1926 built a Rhine crossing with the pylons of Voerde, two masts 138 meters high.
In 1953, the first 345 kV line was put into service by American Electric Power in the United States. In Germany in 1957 the first 380 kV overhead power line was commissioned (between the transformer station and Rommerskirchen). In the same year the overhead line traversing of the Strait of Messina went into service in Italy, whose pylons served the Elbe crossing 1. This was used as the model for the building of the Elbe crossing 2 in the second half of the 1970s which saw the construction of the highest overhead line pylons of the world. Earlier, in 1952, the first 380 kV line was put into service in Sweden, in 1000 km (625 miles) between the more populated areas in the south and the largest hydroelectric power stations in the north. Starting from 1967 in Russia, and also in the USA and Canada, overhead lines for voltage of 765 kV were built. In 1985
Mathematical analysis
An overhead power line is one example of a transmission line. At power system frequencies, many useful simplifications can be made for lines of typical lengths. For analysis of power systems, the distributed resistance, series inductance, shunt leakage resistance and shunt capacitance can be replaced with suitable lumped values or simplified networks.
Short and medium line model
A short length of a power line (less than 80 km) can be approximated with a resistance in series with an inductance and ignoring the shunt admittances. This value is not the total impedance of the line, but rather the series impedance per unit length of line. For a longer length of line (80–250 km), a shunt capacitance is added to the model. In this case it is common to distribute half of the total capacitance to each side of the line. As a result, the power line can be represented as a two-port network, such as with ABCD parameters.[21]
The circuit can be characterized as
where
- Z is the total series line impedance
- z is the series impedance per unit length
- l is the line length
- is the sinusoidal angular frequency
The medium line has an additional shunt admittance
where
- Y is the total shunt line admittance
- y is the shunt admittance per unit length
-
Short length of power line
-
Medium length of power line
See also
- Aerial cable
- Conductor marking lights
- CU project controversy
- Overhead cable
- Overhead line
- Raptor conservation
- Third rail
- Operation Outward
- Powerline river crossings in the United Kingdom
- Wireless monitoring of overhead power lines
References
- ^ ISBN 0-07-020974-X, Chapter 14 Overhead Power Transmission
- ^
Gönen, T. (2014). Electrical Power Transmission System Engineering: Analysis and Design (3rd ed.). CRC Press. ISBN 9781482232233.
- ^ Kynge, James (8 June 2018). "China's global power play". Financial Times. Retrieved 10 June 2018.
- ^ "Powering Up - Vertical Magazine - The Pulse of the Helicopter Industry". verticalmag.com. Archived from the original on 4 October 2015. Retrieved 4 October 2015.
- YouTube
- ^ "Chapter 6. Visual aids for denoting obstacles" (PDF). Annex 14 Volume I Aerodrome design and operations. International Civil Aviation Organization. 2004-11-25. Retrieved 1 June 2011.
6.2.8 ... spherical ... diameter of not less than 60 cm. ... 6.2.10 ... should be of one colour.
- ^ "Polymer insulator manufacturer". NGK-Locke. Archived from the original on 2012-09-05.
- ^ "ABB Energizes Transformer At Record 1.2 Mln Volts". World Energy News. Retrieved 7 October 2016.
- ^ "Advanced Rubber Products - Suspension Insulators". Archived from the original on 2022-03-18. Retrieved 2013-09-17.
- ^ "Economic Choice Of Conductor Size - Kelvin's Law".
- ^ Head, Elan (April 2015). "High-value cargo". Vertical Magazine. pp. 80–90. Archived from the original on 19 April 2015. Retrieved 11 April 2015.
- ^ Maher, Guy R. (April 2015). "A cut above". Vertical Magazine. pp. 92–98. Archived from the original on 12 May 2015. Retrieved 11 April 2015.
- ^ Harnesk, Tommy (9 January 2015). "Helikoptermonterad motorsåg snabbkapar träden". Ny Teknik (in Swedish). Archived from the original on 2015-01-12. Retrieved 12 January 2015.
- ^ Weger, Travis (2017-11-14). "WAPA Helicopters: Saving Time and Money". TDWorld. Retrieved 2017-12-07.
- ^ Grainger, John J. and W. D. Stevenson Jr. Power System Analysis and Design, 2nd edition. McGraw Hill (1994).
- ^ Freimark, Bruce (October 1, 2006). "Six Wire Solution". Transmission & Distribution World. Retrieved March 6, 2007.
- ISBN 9780521878111.
- ^ Beaty, H. Wayne; Fink, Donald G., Standard Handbook for Electrical Engineers (15th Edition) McGraw-Hill, 2007 978-0-07-144146-9 pages 14-105 through 14-106
- ^ Aircraft Accidents Due to Overhead Power Lines
- ^ "Pacific Gas and Electric Company Reminds Customers About Flying Kites Safely". Archived from the original on 2014-10-20. Retrieved 2014-10-20.
- ISBN 978-1-111-42577-7, Chapter 5 Transmission Lines: Steady-State Operation
Further reading
- William D. Stevenson, Jr. Elements of Power System Analysis Third Edition, McGraw-Hill, New York (1975) ISBN 0-07-061285-4
External links
- Media related to Overhead power lines at Wikimedia Commons